360 Power Quality Platinum Series Online UPS 1-3 kVA

The Platinum Series UPS from 360 Power Quality delivers true, double conversion online protection in a convenient rack/tower form factor. Ideal for small data centers, medical labs, light industrial facilities and other applications requiring rugged UPS protection, the Platinum Series supports extended runtime needs with optional EBMs.

 

Rating: 1000-3000 VA Single-Phase UPS

Voltage: 90-208 Vac

Configuration: Rack/Tower

Weight 25.6 lbs
Dimensions 17.3 × 16.2 × 3.4 in
Manufacturer

Phase

Power Rating kVA

Configuration

,

Model

1kVA(L), 1.5kVA(L), 2kVA(L), 2kVA(H), 3kVA(H)

Description

Model

1kVA(L)

1.5kVA(L)

2kVA(L)

2kVA(H)

3kVA(H)

Capacity

1kVA / 1kW 1.5kVA / 1.5kW 2kVA / 2kW 2kVA / 2kW 3kVA / 3kW

Input

Input Voltage Nominal Range 100-120VAC, 90-150VAC, (Low Voltage Units), 200-240VAC, 180-300VAC (High Voltage Units)
Frequency Range 40/70 Hz +/-4%, (Auto sense on startup)
Topology True Online Double Conversion
Input Current THD <9.0%
Power Factor ≧ 0.95 at 100% Load

Output

Phase 1 Phase
Output Voltage / Low- High (L) 100/110/115/120, (H) 200/208 /220 / 230 / 240, NOTE: (L) 120VAC Default, (H) 208V Default
AC Voltage Regulation ± 1% (Normal)
Frequency Range (Sync Range) 46Hz ~ 54 Hz @ 50Hz system, 57Hz ~ 63 Hz @ 60Hz system, (Batt Mode) +/- 0.1% Hz
Overload AC Mode/ 100%~110%: 1 hour; 110%~130%: 1min; >130% : 1sec
Battery Mode 100%~110%: 30sec; 110%~130%: 10sec; >130% : 1sec
Current Crest Ratio 3:1 max
Voltage THD ≦ 2 % @ 100% Linear Load; ≦ 4 % @ 100% Non-linear Load (PF≥0.8)
Step Load Response +/- 4% 50% step load, +/-6% 100% step load, Return +/-3% of nominal (11 cycles)

Efficiency

AC Mode >89% @ fully charged batteries (1-1.5kVA) >91% @ fully charged batteries (2-3kVA)

Battery

Voltage (VDC) 27.4VDC +/-1% 41VDC +/-1% 54.7VDC +/-1% 82.1VDC +/-1%
Battery Backup Time @ 3.5 minutes at full load
Charge Current Default: 2A, Max: 8A Adjustable
Recharge Time 3 hours recovery to 95% capacity for internal battery @ 2A charging current

Physical

Standard Model Dimension, W x D x H (In.) 17.3” x 16.2” x 3.4” 17.3” x 16.2” x 3.4” 17.3” x 24.8” x 3.4” 17.3” x 24.8” x 3.4” 17.3” x 24.8” x 3.4”
Net Weight (lbs) 25.6 lbs 34.2 lbs 43 lbs 43 lbs 61.3 lbs

Bypass

Overload Conditions Continuous below 130%, 1 minute at 130%, 1 cycle at 1000%

Environment

Operation Temperature 0 ~ 40°C
Operation Humidity <95 % and non-condensing
Operation Altitude 2000 ft.
Heat Dissipation (BTU/Hr) 520 877 1171 1000 1500
Acoustic Noise Level
(Front of Unit)
Less than 50dBA @ 1 Meter

Management

Smart RS-232 or USB Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser
MODBUS Card Power Management with MODBUS communication

Agencies

RoHS All units are RoHS compliant
Safety Agencies UL1778 5th Edition, CSA22.2 No.107.3
EMC FCC Part 15J, Class A, IEC 61000-4-2, Electrostatic Discharge, IEC61000-4-3 Level 3 Radiated Electromagnetic Filed immunity. (Additional EMC Agencies listed in User’s Manual).

Additional information

Weight 25.6 lbs
Dimensions 17.3 × 16.2 × 3.4 in
Manufacturer

Phase

Power Rating kVA

Configuration

,

Model

1kVA(L), 1.5kVA(L), 2kVA(L), 2kVA(H), 3kVA(H)