Model |
10kVA(L) |
15kVA(L) |
20kVA(L) |
30kVA(L) |
40kVA(L) |
|
Capacity |
10kVA / 10kW | 15kVA / 15kW | 20kVA / 20kW | 30kVA / 30kW | 40kVA / 40kW | |
Input |
||||||
| Input Voltage – (Range) | 208VAC – (+30%, -17%) | |||||
| Input (THD)i | 1% – 100% Load, 2% – 50% Load | |||||
| Frequency Range | 46Hz ~ 64 Hz | |||||
| Phase | 3 Phase with Neutral | |||||
| Power Factor | ≧ 0.99 at 100% Load | |||||
Output |
||||||
| Phase | 3 Phase with Neutral | |||||
| Output Voltage | 3 x 208/220 VAC (Ph-Ph), 3 x 120/127 VAC (Ph-N) | |||||
| AC Voltage Regulation | ± 1% | |||||
| Frequency Range (Sync Range) | 50/60Hz | |||||
| Overload | AC Mode/ | 100%~110%: 1 hour; 110%~130%: 1min; >130% : 1sec | ||||
| Battery Mode | 100%~110%: 30sec; 110%~130%: 10sec; >130% : 1sec | |||||
| Current Crest Ratio | 3:1 max | |||||
| Harmonic Distortion | ≦ 2 % @ 100% Linear Load; ≦ 4 % @ 100% Non-linear Load (PF≥0.8) | |||||
| Transfer Time | Line <—> Battery | 0ms | ||||
| Inverter <—> Bypass | 0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass) | |||||
Efficiency |
||||||
| AC Mode | 94% | |||||
| Battery Mode | 93.5% | |||||
| ECO Mode | 97% | |||||
Physical |
||||||
| Standard Model | Dimension, W x D x H (In.) |
9.8” x 27” x 33” | 12” x 34” x 40” | 9.8” x 28.2” x 32.5” | ||
| Net Weight (lbs) | 209 lbs | 398 lbs | 508 lbs | 979 lbs | ||
| Shipping Information | Dimension, W x D x H (In.) |
15” x 31.9” x 49.6” | 17.1” x 37.8” x 49.6” | 28” x 40.8” x 74.9” | ||
| Net Weight (lbs) | 242 lbs | 517 lbs | 1177 lbs | |||
| External Battery Cabinets | TBA | Optional | ||||
Environment |
||||||
| Operation Temperature | 0 ~ 40°C (the battery life will down when > 25°C) | |||||
| Operation Humidity | <95 % and non-condensing | |||||
| Operation Altitude ft/(m) | 3,300 ft., (1000) | |||||
| Acoustic Noise Level (Front of Unit) |
Less than 54dB @ 1 Meter | |||||
Management |
||||||
| Smart RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC | |||||
| MODBUS | Supports MODBUS for Industrial Applications | |||||
| Optional SNMP | Power management from SNMP manager and web browser | |||||
Approval Agencies |
||||||
| All Agency Approvals | UL1778 (5th Edition), cUL, CSAc 22.2 EC 62040-1 UPS Standards EMI Compatibility: FCC Title 47, Part 15, Subpart B Seismic/OSHPD (2022) |
|||||
360 Power Quality Diamond Series Three-Phase UPS 10-40 kVA
The Diamond Series three-phase UPS from 360 Power Quality provides optimal protection in one of the smallest footprints in the industry, enabling it to fit into small locations where space is at a premium. With the ability to increase capacity and performance by operating in parallel with up to six units, the Diamond Series features an output power factor of 1.0, ensuring higher kW output with its advanced IGBT performance.
Rating: 10-40 kVA Three-Phase UPS
Voltage: 208 Vac
Configuration: Tower
| Weight | 209 lbs |
|---|---|
| Dimensions | 9.8 × 27 × 33 in |
| Manufacturer | |
| Phase | |
| Power Rating kVA | |
| Configuration | |
| Model | 10kVA(L), 15kVA(L), 20kVA(L), 30kVA(L), 40kVA(L) |
Additional information
| Weight | 209 lbs |
|---|---|
| Dimensions | 9.8 × 27 × 33 in |
| Manufacturer | |
| Phase | |
| Power Rating kVA | |
| Configuration | |
| Model | 10kVA(L), 15kVA(L), 20kVA(L), 30kVA(L), 40kVA(L) |