Nationwide Service on All UPS Equipment
24/7 Support: (877) 469-4846

GNB Telecom Batteries

Unified Power offers a comprehensive range of valve-regulated lead acid (VRLA) and flooded batteries to serve the telecommunications market.

These battery ranges are designed for remarkable performance, long life, high energy density and ease of installation, which makes them applicable for all types of telecom applications.

Absolyte GP Series
Absolyte GX Series

Design life in years: 20 @ 25°C
Nominal capacity: 104–4800 Ah @ 25°C
Grid plate
Single cell
Valve regulated lead-acid batteries
Maintenance-free (no topping-up)
Special high current performance
Recyclable

  • System ampere-hour range – 104 to 4800 Ah to 1.75 VPC at 8-hour rate @ 25°C (77°F).
  • Electrolyte – 1.310 specific gravity acid (nominal).
  • Safety vent – 3-10 psi opening pressure, self-resealing.
  • Terminals – Solid copper insert.
  • Positive plate – Patented lead calcium tin silver alloy.
  • Negative plate – Lead calcium grid alloy.
  • 20 years design life in float applications at 25°C (77°F)
  • 1200 cycles to 80% DOD at 25°C (77°F)
  • Operating temperature – Temperature excursions between -40°C (-40°F) to +50°C (122°F) allowed (battery performance and life will be affected).
  • Self-discharge – 0.5 to 1% per week maximum @ 25°C (77°F).
  • Float voltage – 2.23 to 2.27 VPC.
  • Container and Cover – Polypropylene is standard. Flame retardant, UL94 V-0/28% L.O.I. is optional.
  • Enhanced post access for maintenance and battery health assessment

Design life in years: 20 @ 25°C
Nominal capacity: 104–4800 Ah @ 25°C
Grid plate
Single cell
Valve regulated lead-acid batteries
Maintenance-free (no topping-up)
Special high current performance
Recyclable

  • System ampere-hour range – 104 to 4800 Ah to 1.75 VPC at 8-hour rate @ 25°C (77°F).
  • Electrolyte – 1.310 specific gravity acid (nominal).
  • Safety vent – 3-10 psi opening pressure, self-resealing.
  • Terminals – Solid copper insert.
  • Positive plate – Patented lead calcium tin silver alloy.
  • Negative plate – Lead calcium grid alloy.
  • 20 years design life in float applications at 25°C (77°F)
  • 1200 cycles to 80% DOD at 25°C (77°F)
  • Operating temperature – Temperature excursions between -40°C (-40°F) to +50°C (122°F) allowed (battery performance and life will be affected).
  • Self-discharge – 0.5 to 1% per week maximum @ 25°C (77°F).
  • Float voltage – 2.23 to 2.27 VPC.
  • Container and Cover – Polypropylene is standard. Flame retardant, UL94 V-0/28% L.O.I. is optional.
  • Enhanced post access for maintenance and battery health assessment
Quick Quote
Or call (240) 772-1710 for immediate help.